RSLogix 5000 version 17 or greater must be used for the 1734-AENTR
Add-on Profile. The 1734-AENTR adapters will accept I/O connections with the electronic keying for the 1734-AENT. This allows the 1734-AENTR adapter to be used in a daisy-chain topology with the 1734-AENT profile used for the 1734-AENTR.

 

If using the adapter with a 1756-ENBT module, 1768-ENBT module or an L3xE processor, use the following required firmware versions for these bridge modules:

  1. 1756-ENBT firmware version 4.5 or greater
  2. 1768-ENBT firmware version 2.1 or greater
  3. L3xE processor firmware version 17 or greater

If you use the BootP utility to assign IP addresses to the adapter, use version 2.3.2 or greater.

 

Establish I/O Connections

When you start a POINT I/O system and establish I/O connections, the outputs transition to the Idle state, applying Idle state data before going to Run mode. This occurs even when the controller making the connection is already in Run mode.

Configure Autobaud

The adapter cannot reconfigure an I/O module that you previously configured to operate at a fixed baud rate. When you reuse a POINT I/O module from another POINT I/O system, configure the module to autobaud before using it with the adapter.

~ General ~
  • Weight, approx.280 g (0.62 lb)
  • Input voltage rating 10…28.8V DC range
  • Inrush current 6 A max for 10 ms
  • Ethernet ports 2 - configured as Embedded Switch
  • Ethernet connector RJ-45,
~ Expansion I/O capacity~
  • 1734-AENTR backplane current output = 0.8 A.
  • 63 modules max
  • 20 direct connections max
  • Actual number of modules can vary
~ POINTBus current requirements ~
  • 75 mA 1734-IB2, 1734-IB4, 1734-IB8, 1734-IV2, 1734-OB2
  • 80 mA (Catalog number 1734-OW2)
  • 100 mA (Catalog number 1734-OX2)
  • 110 mA (Catalog number 1734-SSI)
  • 160 mA (Catalog number 1734-IJ2)